Water Fill Station: Test and Calibrate the Flow Rate

Water Fill Station - Testing and Determining the Flow Rate

Testing System Operation

1) Place key-fob on reader until a single beep is heard.

2) Pump will start once authorized (two beeps will signal authorization; fob reader will illuminate red).

3) To stop pump, place key-fob on reader until single beep is heard.

4) Red light is no longer illuminated. Pump is now off.

Notes
If multiple beeps are heard, it would indicate the fob is not authorized. Contact administrator to confirm and correct.

Certification of Installation (For Installer)

Alert
Upon completion of installation, please provide our office with photos of the finished product by emailing them to support@conxwireless.com or by text to 306-979-8900. These photos MUST be sent to our office PRIOR to leaving the site. We require photos of the following:
  • Device placement
  • All wiring connections from device to relay
  • All wiring connections from relay to pump
  • Plug-in power supply into surge protected panel
  • All wiring connections from flow sensor to our relay (if applicable)
  • All wiring connections from flow sensor to power (if applicable)

Determining Flow Rate/Volume

Notes
Water volume is determined by either volumetric method (formula using time x flow rate) or using an in-line flow-rate sensor (wired voltage measurements).

1) Volumetrics (no flow-rate sensor)

You will require a quantifiable measured receptacle and a timer. Place the hose from the pump into the receptacle. Activate the pump for a total of 60 seconds (if possible). When 60 seconds is up, shut off the pump and measure how much water was dispersed during that period. That number will then be entered as your flow rate (L/min).

2) In-line Flow-rate Sensor (with volume read out)

Activate the pump for a total of 90 seconds. When 90 seconds is up, shut off the pump. Report the results to your Administrator.

  • Our WFS is compatible with mechanical, magnetic, and ultrasonic flow rate sensors with a 4-20mA or 0-5V signal output.
  • Conversion Calculator
    1 US Gallon = 3.78541 Liters
    1 Imperial Gallon = 4.54609 Liters

Setting the Flow Rate via Volumetrics

Step 1: At the Command Center, under ‘All’, select Pump Station>Settings.

Step 2: At the Pump Center, select ‘Settings’.

Step 3: In your Pump Settings, click on the Pump Stations tab and select your WFS from the device list on the left.

Once selected, enter the flow rate (L/min) into the box provided. If the reported volume was not measured in Liters, please see the conversion calculator to adjust accordingly. Once you have entered in the flow rate, select ‘Save Device’.

Step 4: Your screen will refresh upon selecting ‘Save Device’. Select your WFS from the list to confirm that your flow rate has been set.

Setting the Flow Rate via Flow Sensor

Step 1: At the Command Center, under ‘All’, select Pump Station>Settings.

Step 2: At the Pump Center, select ‘Settings’. You will then be directed to your Pump Settings.

Step 3: In your Pump Settings, select the Pump Stations tab. Enter the reported volume (seen on the flow sensor) from the most recent WFS transaction into the box provided. Once entered, select ‘Calibration’.

Notes
  • If the reported volume was not measured in Liters, please see the Conversion Calculator to adjust accordingly.
  • The reported volume must be obtained directly from the flow sensor reading. Please make sure that there is correspondence between both parties at the time of calibration.

Step 4: A pop-up will appear stating that the external flow rate has been saved. Your WFS has now been calibrated with the flow sensor.